short circuit test of transformer in hindi | short circuit test of transformer | practical | test
Summary
TLDRThe script discusses the process of performing a short circuit test on a transformer, focusing on the primary, winding, and high voltage binding. It explains the use of a voltmeter and wattmeter to measure the rated voltage and current, applying a reduced voltage to induce a small current for detecting short circuits. The video will guide viewers through the switch connection diagram, the calculation of copper loss, and the importance of measuring parameters like resistance and inductance. It encourages viewers to subscribe for regular updates on electrical testing techniques.
Takeaways
- ⚡ Short circuit test is performed on the primary winding and high voltage binding of the transformer to determine copper loss efficiency and transformer equivalent resistance impedance.
- 📊 In the short circuit test, voltmeter, ammeter, and wattmeter are connected to the high voltage side of the transformer.
- 🔌 A small percentage (5-10%) of the rated voltage is applied using an autotransformer during the short circuit test.
- 🔋 The secondary or low voltage side remains shorted during the short circuit test.
- 📉 The ammeter measures the current, and the wattmeter measures the copper loss during the short circuit test.
- 🧲 The magnetic flux depends on the applied voltage; reduced voltage results in less magnetic flux and, consequently, lower core losses.
- 🔍 The wattmeter indicates copper losses since the reduced magnetic flux causes minimal iron losses during the test.
- 🔗 The equivalent resistance and impedance are determined using the measured parameters from the short circuit test.
- 📐 Copper losses are directly proportional to the current, while core losses depend on the voltage and magnetic flux.
- 🔔 Viewers are encouraged to subscribe to the channel and press the bell icon for regular updates and more detailed explanations on various topics.
Q & A
What is the purpose of performing a short circuit test on a transformer?
-The purpose of performing a short circuit test on a transformer is to determine copper losses, efficiency, and the equivalent resistance and impedance of the transformer.
Which components are connected on the high voltage side during a short circuit test?
-During a short circuit test, a voltmeter, ammeter, and wattmeter are connected on the high voltage side of the transformer.
How is the voltage applied during the short circuit test?
-In the short circuit test, a voltage that is 5-10% of the rated voltage is applied using an autotransformer to the high voltage side of the transformer.
What happens to the secondary or low voltage side during the short circuit test?
-During the short circuit test, the secondary or low voltage side is short-circuited.
Why is the applied voltage in the short circuit test very low?
-The applied voltage is very low to ensure that the magnetic flux created is minimal, leading to reduced core and iron losses.
What is the role of the wattmeter in the short circuit test?
-The wattmeter measures the copper losses in the transformer during the short circuit test.
How is the rated current applied during the short circuit test?
-The rated current is applied to the circuit by adjusting the voltage from the autotransformer to ensure that the current flowing is at the rated value.
What does the wattmeter measure during the short circuit test?
-The wattmeter measures the power loss due to the copper losses in the transformer.
How is the equivalent resistance of the transformer calculated in the short circuit test?
-The equivalent resistance is calculated using the power loss measured by the wattmeter and the rated current, with the formula P = I^2 * R.
What parameters can be determined from the short circuit test?
-From the short circuit test, the copper losses, equivalent resistance, and impedance of the transformer can be determined.
Outlines
🛠️ Transformer Short Circuit Test Basics
This paragraph introduces the primary aspects of short circuit testing for transformers, focusing on the transformer's windings and high voltage bindings. It explains the purpose of the test, which is to determine the transformer's equivalent resistance and inductance. The script mentions the use of a voltmeter and wattmeter in the high voltage side connection diagram for the short circuit test, and how a rated voltage of 5-10% is applied to the circuit. It also touches on the importance of measuring the magnetic flux, which depends on the supply voltage, and how reduced magnetic flux leads to lower losses and less speed in the transformer.
Mindmap
Keywords
💡Short Circuit Test
💡Copper Loss
💡Equivalent Resistance
💡Impedance
💡Rated Voltage
💡Wattmeter
💡Voltmeter
💡Ammeter
💡Autotransformer
💡Magnetic Flux
Highlights
The primary, winding, and high voltage binding of the 168 test transformer perform the short circuit test.
A voltmeter and wattmeter are connected to the high voltage side for the short circuit test of the transformer.
Another transformer is connected to the high voltage side to help apply a rated voltage of 5 to 10 percent in the circuit.
The secondary side and low voltage side are kept soft during the test to avoid any current flow.
The test involves measuring the reduced magnetic flux which depends on the supply voltage.
A reduced magnetic flux results in lower core speed and consequently less iron loss due to the reduced current.
The short circuit test helps in determining the copper loss, which is observed through the wattmeter.
The rated current of the transformer during the short circuit test is applied to calculate the copper loss.
Losses in the circuit are calculated using the equation for copper loss, denoted by PC.
The equation for copper loss involves the square of the current and the resistance of the coil.
The supply board is used to major the losses in the circuit, which are then measured by the wattmeter.
The short circuit test involves folding only the branch parameters, which are then calculated for the CS and its notches.
The test determines the under root value of the CS, which is essential for understanding the performance of the transformer.
The transformer's performance is analyzed based on the current and voltage dependencies during the short circuit test.
The short circuit test plates are performed to remind the current and voltage dependencies.
The video encourages viewers to subscribe for regular updates on electrical engineering topics.
Transcripts
[संगीत]
168 टेस्ट ट्रांसफार्मर के प्राइमरी
वाइंडिंग और हाई वोल्टेज बाइंडिंग पर
परफॉर्म होता है शॉर्ट सर्किट टेस्ट कॉपर
लोस इफिशिएंसी और ट्रांसफार्मर
इक्विवेलेंट रेजिस्टेंस इंपीडेंस एंड लिए
के जरिए टेंस को डिटरमाइंड करने के लिए
परफॉर्म किया जाता है
तो इस वीडियो में ट्रांसफार्मर के शॉर्ट
सर्किट टेस्ट को डिटेल में समझेंगे
कि इफ यू आर यू ओन दिस Channel Please
subscribe this Channel and press Bell
Icon for regular updates
को स्विच कनेक्शन डायग्राम फॉर शॉर्ट
सर्किट टेस्ट ऑफ़ ट्रांसफार्मर में शॉर्ट
सर्किट टेस्ट में वोल्टमीटर एमिटर वाटमीटर
को हाई वोल्टेज साइड कनेक्ट करते हैं
इसमें एक और ट्रांसफार्मर हाई वोल्टेज
साइड कनेक्ट रहता है जिसकी हेल्प से रेटेड
वोल्टेज का 510 परसेंट वोल्टेज इस सर्किट
में अप्लाई करते हैं मतलब अगर इस
ट्रांसफार्मर का रेट वोल्टेज
500ml है तो ऑटोट्रांसफॉर्मर के हिसाब से
फाइव बोर्ड का 510 परसेंट वोल्टेज हाई
वोल्टेज साइड अप्लाई करते हैं जो कि बहुत
अ स्माल वैल्यू होता है एंड इस वैल्यू को
पॉइंट मीटर में जरूर करता है हम लोग शॉर्ट
सर्किट एस परफॉर्म कर रहे हैं इसलिए
सेकंडरी साइड और लो-वोल्टेज साइड सॉफ्ट
रहता है
ऑफिसर कि टेस्ट में ए कंट्रीवाइड को हम
लोग हाई वोल्टेज साइड कंप्यूटर के थे जो
कि ओपन था पर यहां पर स्कैन रिमाइंड है लो
वोल्टेज साइड है
यहां पर जो अ मीटर है वह सर्किट में स्लो
होने वाली करंट को मैं जरूर करता है
एंड वॉटर मीटर है वह इसमें होने वाले
लोगों से इसको मेजर करता है एस वे नो जो
मैग्नेटिक फ्लक्स है वह सप्लाई वोल्टेज पर
डिपेंड रहता है एंड यहां पर हम लोग और
ट्रांसफॉर्मर्स हेल्प से बहुत कम वैल्यू
का वोल्टेज अप्लाई कर रहा है जिसके कारण
मैग्नेटिक फ्लक्स भी कम क्रिएट होगा एंड
कौर के थ्रू सर्कुलेट करेगा सेंस जो को
रिलैक्स और आयरन लॉस होता है वह मैग्नेटिक
फ्लक्स पर डिपेंड रहता है मतलब यहां पर
रिड्यूस्ड वोल्टेज के कारण लेस मैग्नेटिक
फ्लक्स क्रिएट हो रहा है तो कर लो स्पीड
बहुत कम होगा अब
है तो शॉर्ट सर्किट में ओर लॉस कम लोग
निकले सेट कर देते हैं ड्यू टो इट्स
निकलेंगी बनावट तो जो वाटमीटर है वह कॉपर
लॉस को नजर करेगा
शॉर्ट सर्किट टेस्ट में ट्रांसफार्मर का
जो रेट करंट है सपोच पति एंपियर तो 430
एंपियर सर्किट में अप्लाई करते हैं तीन
चौकों पर लॉस होता है और आयुष व आप लोस जो
करंट के व्यक्ति पर डिपेंड रहता है सो
रिलेटिड करंट के कारण सर्किट में जो को
ऊपर लास्ट प्रोड्यूस होता है उसको वाटमीटर
हेल्प से नजर करते हैं
इक्वेशन ऑफ कॉपर लोशन हेयर को प्रोसेस
डिनोटेड बाय पीसी एंड मीनिंग आफ एग्स कॉपर
लॉट्स आफ लॉर्ड इज इक्वल टू
वन एसिड व एससी को फांसी
जो हेयर को सफेद अ पावर फैक्टर दैट इज ए
गर्ल बिटवीन वोल्टेज एंड करंट तो यहां पर
जो को फलों है उसको वाटमीटर मेजर करें का
यह सप्लाई बोर्ड इसको यहां पर वर्ल्ड मीटर
मेजर करें का या एंड रैपिड करंट को मीटर
में जरुर करेगा एंड इनवेलिड्स कि हेल्प से
हम लोग सिर्फ ब्रांच पैरामीटर्स को फोल्ड
करते हैं यस आर नॉट वन एंड इट्स नॉट वन तो
आर नॉट वन हो जाएगा डब्ल्यूएससी पॉर्न
आईएस क्लियर एंड इंपीडेंस जेट वन के लिए
हम लोग लिखेंगे भी वन एसी अप फॉर ए सीन
फ्रॉम स्लो एंड यहां पर एक नेटवर्क हम लोग
इजली निकाल पाएंगे तो इस नोट वन होगा यहां
अंडर रूट जेड1 का त्यौहार
आदि संसार यूज्ड फॉर उस एंड थ्री पोर्शन
का बात करें शॉर्ट सर्किट टेस्ट कॉपर
प्लेट्स को रिमाइंड करने के लिए परफॉर्म
करते हैं कि एंड जो कॉपर होता है वह करंट
केवल ऊपर डिपेंड करता है कि को लोस
वोल्टेज केवल ऊपर डिपेंड करता है
तो इस तरह से कोई भी टॉपिक को अगर आप इजी
वे समझना चाहते हैं तो चैनल को सब्सक्राइब
कर लें और बेल आइकन को भी प्रेस कर लें
ताकि वीडियोस आप तक पहुंच सकें अ
हुआ है
[संगीत]
関連動画をさらに表示
Video Pembelajaran Modul 4 & 5 Praktikum Rangkaian Listrik 2024/2025 (FH)
DC Series circuits explained - The basics working principle
Praktikum Sistem Daya Elektrik Percobaan I (Transmisi Pendek)
HUKUM II KIRCHHOFF
Electric Circuits: Basics of the voltage and current laws.
SOP Penggunaan Multimeter dan Power Supply
5.0 / 5 (0 votes)