PLC OMRON CP1E | CARA PASANG INPUT OUTPUT
Summary
TLDRThis video tutorial from the 'jago listrik' channel focuses on the installation of input and output components for the Omron CP1E PLC. It explains that inputs are typically on top and outputs below, with the unique requirement for a DC 24-volt supply instead of the usual AC. The presenter demonstrates how to convert 220-volt AC from the power supply to the necessary DC voltage using a power supply unit. The video also covers wiring the input and output components, highlighting the connection of a common (COM) terminal for all inputs and separate COM terminals for different output ranges, ensuring viewers understand the setup for the Omron CP1E PLC.
Takeaways
- 🔌 The video discusses the installation of input and output components on an Omron CP1E PLC.
- 📌 Inputs are typically placed above and outputs below on the PLC, with the supply input voltage being a key consideration.
- ⚡ The Omron CP1E uses DC voltage for inputs, specifically 24 volts DC, differing from the common AC voltage used in other PLCs.
- 🔄 A power supply unit is necessary to convert 220 Volt AC from the mains to the required 24 Volt DC for the PLC.
- 🔗 The wiring of the power supply involves connecting the LN (Line) and ground to the AC source and the output to the PLC's positive and negative terminals.
- 🔩 The input components, such as push buttons, are connected to the DC power supply's positive voltage, while the common (COM) terminal is connected to the negative voltage.
- 🔑 A single COM terminal is used for all inputs, simplifying the wiring process for inputs.
- 💡 The video provides a practical example of connecting a normally closed (NC) push button to an input address and an output to a specific address.
- 🔑 For outputs, each set of outputs has its own COM terminal, which is different from the input's single COM terminal setup.
- 🛠️ The video explains how to wire outputs to the corresponding output addresses on the PLC, with each output having its own designated address.
- ❓ The presenter invites viewers to ask questions in the comments if they need further clarification.
Q & A
What is the main topic discussed in the video?
-The main topic discussed in the video is the installation of input and output components on an Omron CP1E PLC.
What is the difference between the input voltage for Omron CP1E PLC and other PLCs?
-The Omron CP1E PLC uses a DC voltage of 24 volts for its inputs, unlike other PLCs which typically use AC voltage for inputs.
Why is it necessary to convert AC voltage to DC for the Omron CP1E PLC?
-It is necessary to convert AC voltage to DC for the Omron CP1E PLC because its input components require a DC voltage of 24 volts.
What is the role of a power supply in the setup described in the video?
-The power supply is used to convert the AC voltage from the mains (220 Volt AC) to the required DC voltage (24 Volt DC) for the PLC's input components.
How are the input components connected to the Omron CP1E PLC?
-The input components are connected to the Omron CP1E PLC by linking the common (COM) terminal to the negative polarity of the DC power supply and connecting the input devices to the positive DC voltage.
What is the purpose of the COM terminal in the context of the video?
-The COM terminal is used as a common connection point for all input addresses from 00 to 11, allowing a single COM connection for all inputs.
How does the wiring for input components differ from output components on the Omron CP1E PLC?
-For input components, there is only one COM for all input ports, whereas for output components, there are multiple COMs (1, 2, 3, and 4), each serving different ranges of output addresses.
What is the significance of the thick white line mentioned in the video?
-The thick white line signifies the limit for each output COM, indicating that each output has its own dedicated COM terminal and should not be mixed with others.
How are the output components connected to the Omron CP1E PLC?
-The output components are connected by linking the respective COM terminal to the negative polarity of the DC power supply and connecting the load or device to the corresponding output port.
What is the address format for outputs on the Omron CP1E PLC as described in the video?
-The address format for outputs on the Omron CP1E PLC is 'Q' followed by the slot number and the channel number, such as Q100.00 for output 00.
What does the video suggest for viewers who are not clear about the content?
-The video suggests that viewers who are not clear about the content can leave a comment below for further clarification.
Outlines
🔌 Installation of Input/Output Components on Omron CP1E PLC
This paragraph discusses the installation of input and output components on the Omron CP1E PLC. The presenter explains that inputs are typically placed above and outputs below. A crucial point to note is that the input voltage for this PLC model is DC, specifically 24 volts DC, differing from the usual AC input voltage in PLCs. To match this requirement, a power supply is needed to convert the standard 220-volt AC from the power grid to 24 volts DC. The wiring for the power supply involves connecting the LN and ground to the AC source and the output to the PLC's positive and negative terminals. For the input components, a common (COM) terminal is used for all inputs from 00 to 11, connected to the negative DC voltage. An example given is connecting a normally closed (NC) push button to the positive DC voltage and the output push button to an output address, such as 01, which corresponds to the address i1001. The process is straightforward and helps in understanding how to set up the input components for the Omron CP1E PLC.
🔗 Wiring Techniques for Omron CP1E PLC's Input and Output
The second paragraph continues the discussion on the wiring of the Omron CP1E PLC, focusing on the output components. Unlike the single common terminal for all input ports, the outputs have multiple common terminals, each serving different output ranges. For instance, one common terminal is for output 00, another for outputs 01 to 03, and so on, up to output 07. Each output has its own common terminal, which is limited by a thick white line on the PLC. The wiring process for the outputs is similar to that of the inputs, connecting the common terminal to the negative voltage of the power supply. The presenter uses examples to illustrate how to connect a light or load to the output ports, such as connecting a light to the positive voltage of the power supply and the other side to an output port like 00, which corresponds to the address q100.00. The paragraph concludes with an invitation for viewers to ask questions in the comments if they need further clarification and a promise to meet again in the next video.
Mindmap
Keywords
💡PLC
💡Input
💡Output
💡Omron CP1E
💡Power Supply
💡DC Voltage
💡Wiring
💡Push Button
💡Common (COM)
💡Polarity
💡Address
Highlights
Introduction to Omron CP1E PLC and its components setup
Explanation of input and output component placement on the PLC
Note on the standard placement of inputs above and outputs below on PLCs
Emphasis on the importance of matching input voltage to the PLC version
Clarification that Omron CP1E uses DC 24V for inputs, differing from typical AC inputs
Requirement to convert AC 220V to DC 24V for the PLC
Use of a power supply to convert AC to DC voltage
Wiring instructions for the power supply to connect to AC source
Connection of DC output to the PLC's positive and negative terminals
Simplification of input wiring with a single common (COM) for all inputs
How to wire a push button as an input to the DC positive voltage
Connecting the output of a push button to a specific output address on the PLC
Method for observing the input to help with subsequent output connections
Difference in wiring for outputs compared to inputs, with multiple COMs for different output ranges
Connection of the COM to the negative power supply voltage
Wiring a light to the DC positive voltage and connecting the load to the output port
Addressing of the output based on the used COM and output port
Encouragement for viewers to ask questions in the comments for further clarification
Transcripts
kembali lagi di channel jago listrik
kali ini kita akan membahas tentang
versi lagi nih teman-teman tepatnya PLC
Omron cp1e penampakannya seperti ini
jadi kali ini saya akan menjelaskan
Bagaimana pemasangan komponen input
output pada PLC cp1e ini teman-teman
menggunakan ilustrasi Oke kita langsung
aja nah seperti versi-versi sebelumnya
yang saya jelaskan input selalu di atas
sedangkan output itu di bawah nah yang
perlu diperhatikan pada setiap versi
apapun mereknya itu adalah supply input
tegangan ke versinya teman-teman nah
pada penjelasan saya yang sebelumnya itu
rata-rata input tegangan plc-nya
tegangan AC ya teman-teman Nah berbeda
dengan versi Omron cp1i ini pada versi
ini inputnya adalah tegangan DC tepatnya
24 volt DC jadi supaya sesuai dengan ke
versi ini harus 24 volt sih teman-teman
Nah karena ini memerlukan tegangan DC
jadi kita harus merubah dulu tegangan
PLN 220 Volt AC ke tegangan DC 24 volt
ya teman-teman Nah caranya gimana kita
bisa menggunakan power supply ya Nah
power supply ini berfungsi untuk merubah
tegangan AC ke tegangan DC nah cara
wiring power supply ini seperti ini pada
kode LN dan ground itu kita hubungkan ke
sumber tegangan AC atau PLN ya 220 Volt
AC l itu fasa and Itu netral dan
sebelahnya itu ground sedangkan
outputnya itu berupa DC teman-teman ada
feminin V plus nah V plus itu polaritas
plus dan feminin polaritas Min nah ini
kita hubungkan yang V plus ke plusnya
PLC dan PMI ke femininnya versi nah
seperti ini plus ke plus - teman-teman
sedangkan ground-nya langsung yang ada
lambang groundnya nah bagaimana dengan
komponen inputnya nah ini simpel aja
kalau kita lihat di sini ada com ya
teman-teman com ini tepat masukkan untuk
semua alamat input dari
00 sampai 11 Jadi cukup satu com untuk
semua input nah ini kita hubungkan dulu
com ini ke tegangan DC yang polaritas
minus seperti ini Nah ini teman-teman
bisa ambil dari minus atau langsung dari
minusnya power supply ya teman-teman
setelah ini kita bisa langsung memasang
komponen inputnya nah contohnya berupa
push button NC bagian input button kita
hubungkan ke tegangan plus dc-nya
sedangkan yang output push button kita
hubungkan ke alamat output 01 contohnya
nah ini terserah teman-teman
menghubungkan yang mana Kebetulan saya
di sini 01 maka alamatnya
i1001 begitu cara pengamatan inputnya
membantu output selanjutnya sama saja
seperti ini contohnya push button NU
yang atasnya kita ambil dari polaritas
plus tegangan DC power supply silahkan
yang bawahnya langsung kita hubungkan ke
port inputnya yang 08 jadi alamatnya
i10.08 begitu teman-teman Gampang ya Nah
selanjutnya yang outputnya ada perbedaan
sedikit input 1com untuk semua port
inputnya sedangkan pada output itu ada
beberapa com ada 1 2 3 dan 4 nahkom ini
untuk output 00 sedangkan com ini untuk
output 01 com yang ini untuk output 0203
sedangkan com ini untuk output 04 sampai
07 jadi setiap output mempunyai gomnya
sendiri nah ini dibatasi oleh garis
tebal putih ini teman-teman nah cara
menghubungkannya sama seperti input
comnya kita hubungkan ke polaritas
negatif power supply-nya tegangannya nah
seperti ini
nah Kebetulan saya memakai com yang ini
jadi output ya saya pakai yang nol
teman-teman nah seperti ini
Nah jadi lampu sehubungkan ke tegangan
DC prioritas + power supplynya sedangkan
bagian Sisi satunya beban atau lampu
saya hubungkan ke port output 00 nya
karena saya memakai com yang ini jadi
alamatnya bisa seperti ini
q100.00 nah output berikutnya sama saja
misalkan Saya memakai com yang ini ya
teman-teman Yang ini sama kita ambil
dari negatifnya tegangan DC Nah jadi
saya harus memakai output 02 atau 03
atau kedua-duanya ya teman-teman Nah di
sini Saya memakai yang 03 maka alamatnya
q100.03 itu juga selanjutnya
Saya memakai Komeng ini jadi saya
memakai output 04 sampai 06 ya Nah
seperti ini saya pakai yang 06 jadi
q100.06 nah begitu caranya wiring input
dan output pada versi obrolan cv1e ini
teman-teman Nah bagi teman-teman yang
belum paham bisa komen bawah dan sampai
jumpa di video selanjutnya see you
teman-teman
Voir Plus de Vidéos Connexes